IFC 4.3.2.20241204 (IFC4X3_ADD2) under development

CoefficientOfPerformanceCurve

Semantic definition

Chiller coefficient of performance (COP) is function of condensing temperature and evaporating temperature, data is in table form, COP= f (TempCon, TempEvp), COP = a2+b2*Tei+c2*Tei\^2+d2*Tci+e2*Tci\^2+f2*Tei*Tci. This table uses multiple input variables; to represent, both DefiningValues and DefinedValues lists are null and IfcTable is attached using IfcResourceConstraintRelationship and IfcMetric. Columns are specified in the following order: 1.IfcPositiveRatioMeasure:CoefficientOfPerformance 2.IfcThermodynamicTemperatureMeasure:CondensingTemperature 3.IfcThermodynamicTemperatureMeasure:EvaporatingTemperature

Referenced in
Pset_ChillerTypeCommon
Table A

Edit on Github


Is this page difficult to understand? Let us know!