IFC 4.3.2.20240904 (IFC4X3_ADD2) under development

7.5.4.26 Pset_CooledBeamTypeCommon

7.5.4.26.1 Semantic definition

Cooled beam common attributes.

SoundLevel and SoundAttenuation attributes deleted in IFC2x2 Pset Addendum: Use IfcSoundProperties instead.

7.5.4.26.2 Applicable entities

7.5.4.26.3 Properties

Name Property Type Data Type Description
Reference IfcPropertySingleValue IfcIdentifier

Reference ID for this specified type in this project (e.g. type 'A-1'), Also referred to as "construction type". It should be provided as an alternative to the name of the "object type", if the software does not support object types and no classification reference to a recognized classification system used.

Status IfcPropertyEnumeratedValue PEnum_ElementStatus

Status of the element, predominately used in renovation or retrofitting projects. The status can be assigned to as "New" - element designed as new addition, "Existing" - element exists and remains, "Demolish" - element existed but is to be demolished, "Temporary" - element will exists only temporary (like a temporary support structure).

IsFreeHanging IfcPropertySingleValue IfcBoolean

Is it free hanging type (not mounted in a false ceiling)?

PipeConnection IfcPropertyEnumeratedValue PEnum_CooledBeamPipeConnection

The manner in which the pipe connection is made to the cooled beam.

WaterFlowControlSystemType IfcPropertyEnumeratedValue PEnum_CooledBeamWaterFlowControlSystemType

Factory fitted waterflow control system.

WaterPressureRange IfcPropertyBoundedValue IfcPressureMeasure

Allowable water circuit working pressure range.

NominalCoolingCapacity IfcPropertySingleValue IfcPowerMeasure

Nominal cooling capacity.

NominalSurroundingTemperatureCooling IfcPropertySingleValue IfcThermodynamicTemperatureMeasure

Nominal surrounding temperature (refers to nominal cooling capacity).

NominalSurroundingHumidityCooling IfcPropertySingleValue IfcNormalisedRatioMeasure

Nominal surrounding humidity (refers to nominal cooling capacity).

NominalSupplyWaterTemperatureCooling IfcPropertySingleValue IfcThermodynamicTemperatureMeasure

Nominal supply water temperature (refers to nominal cooling capacity).

NominalReturnWaterTemperatureCooling IfcPropertySingleValue IfcThermodynamicTemperatureMeasure

Nominal return water temperature (refers to nominal cooling capacity).

NominalWaterFlowCooling IfcPropertySingleValue IfcVolumetricFlowRateMeasure

Nominal water flow (refers to nominal cooling capacity).

NominalHeatingCapacity IfcPropertySingleValue IfcPowerMeasure

Nominal heating capacity.

NominalSurroundingTemperatureHeating IfcPropertySingleValue IfcThermodynamicTemperatureMeasure

Nominal surrounding temperature (refers to nominal heating capacity).

NominalSupplyWaterTemperatureHeating IfcPropertySingleValue IfcThermodynamicTemperatureMeasure

Nominal supply water temperature (refers to nominal heating capacity).

NominalReturnWaterTemperatureHeating IfcPropertySingleValue IfcThermodynamicTemperatureMeasure

Nominal return water temperature (refers to nominal heating capacity).

NominalWaterFlowHeating IfcPropertySingleValue IfcVolumetricFlowRateMeasure

Nominal water flow (refers to nominal heating capacity).

IntegratedLightingType IfcPropertyEnumeratedValue PEnum_CooledBeamIntegratedLightingType

Integrated lighting in cooled beam.

FinishColour IfcPropertySingleValue IfcLabel

The finish colour of the object.

CoilLength IfcPropertySingleValue IfcPositiveLengthMeasure

Length of coil.

CoilWidth IfcPropertySingleValue IfcPositiveLengthMeasure

Width of coil.

Table 7.5.4.26.A

Edit on Github


Is this page difficult to understand? Let us know!

7.5.4.26.4 Changelog

7.5.4.26.4.1 IFC4

7.5.4.26.4.2 IFC4.2

7.5.4.26.4.3 IFC4.3_DEV_c85b862